MVR FW 210 series F
You’re about to download MVR FW 210 series F
You have chosen to download our software.
Within a few seconds, you will receive an email containing a download link.
Having trouble using the software? Please contact support@deif.com.
Best regards,
DEIF A/S
The software is subject to copyright DEIF A/S
By following the above mentioned link and downloading the file you automatically accept DEIF A/S copyright and license agreement (EULA). The license agreement can be found on www.deif.com/software
This software applies to the following DEIF products:
- MVR-F201 - Basic Feeder Protection
- MVR-F205 - Directional Feeder Protection
- MVR-F210 - Feeder Protection
- MVR-F215 - Directional Feeder Protection
You’re about to download 2.1.1.3-247
The main changes implemented since the last version are as follows:
New features
- Parameter: Settable voltage measurement threshold.
- HMI: Transformer module measurements added to mimic.
- HMI: Imeas/Iset to I2> function.
- HMI: Kazakh, Chinese and Russian language translations.
- Communication: Energy measurement mapping to IEC61850.
- Communication: Scaled analog inputs to IEC104.
- Communication: Voltage and current THD to IEC61850.
- Communication: U3/U4 frequency to IEC61850 and Modbus.
- Communication: CTS2 to IEC61850 mapping.
- Communication: Programmable stages to IEC61850.
Changes
- Synchrocheck [25]: Added LL/DL/LD/DD-mode, ability to select line or bus as reference, additional signals.
Corrections
- mA output: Corrected mA output accuracy.
- Frequent start FSP (N>) [66]:Fixed issue where frequency start -stage was not working correctly.
- AVR: Fixed issue where AVR scaling curve was not working correctly.
- Communication: Fixed issues with IEC61850 Test outs (forced statuses) and events.
- Directional overcurrent (Idir>) [67]: Fixed issue where protection blocking signal reset start signal to zero.
- HMI: Corrected language encoding.
- Synchrocheck: Fixed issue where synchrocheck was not working correctly with maximum settings.
- TrafoModule: Fixed issue where Manual Set vector group was not working correctly.
- General: Improved USW connection termination.
- General: Improved option card detection.
- General: Fixed issue where device discovery announcement message had incorrect serial number.
Ver. | Date | Description |
---|---|---|
2.1.1.3-247 |
10/01/2025 |
New features
Changes
Corrections
|